SL890020
Flow sensors - Consumption measurement for compressed air
The function of the flow sensor is based on the calorimetric principle. The probe is heated up from the inside a few degrees Celsius in relation to the flow medium, in which it protrudes. When the medium flows, the heat generated in the probe is dissipated through the medium. The temperature within the sensor is measured and compared with the likewise measured medium temperature. From the obtained temperature difference the flow state of each medium can be derived. These sensors are applied in areas such as monitoring of cooling systems, ventilation systems, pump dry running by checking the presence of liquid or gas flows.
Electrical properties
- Number of switching outputs
- 1
- Type of switching function
- Normally open contact (NO)
- Type of analog output
- 4 - 20mA
- Type of electrical connection
- Connector M12
- Type of switching output
- Relay contact
- Type of interface connection
- Plug-in connection M12
- Rated switching current
- 150mA
- Setting procedure
- Parameterization
- Coding of interface connection
- A
- Load resistance (current output)
- 500kOhm
- No-load current
- 120mA
- Switching voltage
- 48V
- Measurement principle
- calorimetric
- Number of pins of interface connection
- 5
- Supported communication interface
- Modbus RTU
- Measuring range flow volume
- 0.8 - 105l/min
- Measuring range flow velocity
- 0.18 - 185m/s
- Display
- TFT display
- Short circuit protection, Reverse polarity protection
- 5
- A
Mechanical properties
- Type of process connection
- R1/4 inch
- Design
- Cuboid, integrated measuring section
- Width
- 194mm
- Pressure resistance
- 16bar
- Height
- 174.7mm
- Length
- 75mm
- Medium temperature
- -30 - 80°C
- Degree of protection (IP)
- IP65
- Housing material
- Plastic PC
- Sensing element material
- Stainless steel 1.4301
Other properties
- Relative air humidity (non-condensing)
- 95%
- Ambient temperature
- -20 - 70°C
- Measuring accuracy
- ± 1.5 % of measuring range ± 0.3 % of measuring range end
- Reference medium / object
- Air
- Pneumatic applications
Connection technology
Cable sockets M12 5-pin field attachable
Cable sockets M12 5-wire shielded
Cable sockets M12-socket M12-connector 5-wire
Gateway
Process data acquisition
Other sensors
Protection cap, teflon M8
Recalibration of inline flow sensors
Datasheets
Manuals
Drawings
Interfaces
Product Compliance
-
pdfUKCA declaration of conformityPDF-file, 324 KB
-
pdfMaterial compliancePDF-file, 478 KB
-
pdfEU declaration of conformityPDF-file, 253 KB
-
pdfUL declaration of conformityPDF-file, 254 KB
-
pdfCSA declaration of conformityPDF-file, 243 KB
Product flyers
Whitepapers
-
pdfEnergy monitoring and production / process data acquisitionPDF-file, 918 KB
-
pdfWhitepaper fluid technologyPDF-file, 755 KB
-
pdfWhitepaper pressure consumption measurementPDF-file, 497 KB
-
pdfWhitepaper flow sensorsPDF-file, 426 KB
Application examples
| Classification | Class |
|---|---|
| eClass-7.0 | 27371815 |
| eClass-7.1 | 27371815 |
| eClass-8.0 | 27371815 |
| eClass-9.0 | 27371815 |
| eClass-9.1 | 27371815 |
| ETIM-6.0 | EC002580 |
| ETIM-7.0 | EC002580 |
| Property | Value |
|---|---|
| RoHS‑compliant | Yes |
| Reach-compliant | Yes |
| TSCA-compliant | Yes |
| IPF Product Group | 725 compressed air and leakage measurement |
| packaging dimensions | |
| 5,19kg CO₂e | |
| Customs tariff number | 90268020 |
| WEEE number | 40951076 |