Flow sensors - Consumption measurement for compressed air

SL890020

SL890020
List price
986,50 €
On demand
Sensor flow, air, calorimetric, 175x75x194mm, R 1/4", 12-36V DC, 1x relay contact NO, 4-20mA, M12 plug connector 5-pin, plastic PC, pressure resistance 16bar, with display, parameterization, RS-485
Compare

Flow sensors - Consumption measurement for compressed air

The function of the flow sensor is based on the calorimetric principle. The probe is heated up from the inside a few degrees Celsius in relation to the flow medium, in which it protrudes. When the medium flows, the heat generated in the probe is dissipated through the medium. The temperature within the sensor is measured and compared with the likewise measured medium temperature. From the obtained temperature difference the flow state of each medium can be derived. These sensors are applied in areas such as monitoring of cooling systems, ventilation systems, pump dry running by checking the presence of liquid or gas flows.

Electrical properties

Number of switching outputs
1
Type of switching function
Normally open contact (NO)
Type of analog output
4 - 20mA
Type of electrical connection
Connector M12
Type of switching output
Relay contact
Type of interface connection
Plug-in connection M12
Rated switching current
150mA
Setting procedure
Parameterization
Coding of interface connection
A
Load resistance (current output)
500kOhm
No-load current
120mA
Switching voltage
48V
Measurement principle
calorimetric
Number of pins of interface connection
5
Supported communication interface
Modbus RTU
Measuring range flow volume
0.8 - 105l/min
Measuring range flow velocity
0.18 - 185m/s
Display
TFT display
Short circuit protection, Reverse polarity protection
5
A

Mechanical properties

Type of process connection
R1/4 inch
Design
Cuboid, integrated measuring section
Width
194mm
Pressure resistance
16bar
Height
174.7mm
Length
75mm
Medium temperature
-30 - 80°C
Degree of protection (IP)
IP65
Housing material
Plastic PC
Sensing element material
Stainless steel 1.4301

Other properties

Relative air humidity (non-condensing)
95%
Ambient temperature
-20 - 70°C
Measuring accuracy
± 1.5 % of measuring range ± 0.3 % of measuring range end
Reference medium / object
Air
Pneumatic applications
You can find accessories for SL890020 in these product groups:

Connection technology

Cable sockets M12 5-pin field attachable

Cable sockets M12 5-wire shielded

Cable sockets M12-socket M12-connector 5-wire

Gateway

Process data acquisition

Other sensors

Protection cap, teflon M8

Recalibration of inline flow sensors

Classification Class
eClass-7.0 27371815
eClass-7.1 27371815
eClass-8.0 27371815
eClass-9.0 27371815
eClass-9.1 27371815
ETIM-6.0 EC002580
ETIM-7.0 EC002580
Property Value
RoHS‑compliant Yes
Reach-compliant Yes
TSCA-compliant Yes
IPF Product Group 725 compressed air and leakage measurement
packaging dimensions
5,19kg CO₂e
Customs tariff number 90268020
WEEE number 40951076