SY92F006
Flow sensors - Consumption measurement for various gases
The function of the flow sensor involves the calorimetric principle. The sensor is heated from the inside by a few degrees Celsius relative to the flowing medium into which it extends. When the medium flows, the heat generated in the sensor is dissipated through the medium. The temperature within the sensor is measured and compared with the medium temperature, which is also measured. The flow condition for each medium can be determined from the resulting temperature difference. The application of these sensors includes use as compressed air consumption meters.
Electrical properties
- Type of analog output
- 4 - 20mA
- Type of electrical connection
- Connector M12
- Type of interface connection
- Plug-in connection M12
- Setting procedure
- Parameterization
- Coding of interface connection
- A
- Load resistance (current output)
- 500kOhm
- No-load current
- 120mA
- Measurement principle
- calorimetric
- Number of pins of interface connection
- 5
- supported communication interface
- MBus, modbus RTU
- Measuring range flow volume
- 8.33 - 4,833.33l/min
- Measuring range flow velocity
- 0.18 - 185m/s
- Display
- TFT display
- protection functions
- short circuit protection, reverse polarity protection
- Number of pins of the electrical connection
- 5
- Electrical connection code
- A
- Operating voltage
- Electrical connection
mechanical properties
- Type of process connection
- R1 inch
- Design
- Cuboid, integrated measuring section
- Width
- 475mm
- Pressure resistance
- 40bar
- Height
- 182.6mm
- Length
- 75mm
- Medium temperature
- -30 - 80°C
- Degree of protection (IP)
- IP65
- Housing material
- plastic PC
- Sensing element material
- Stainless steel 1.4301
- dimensions
other properties
- Relative air humidity (non-condensing)
- 95%
- Ambient temperature
- -20 - 70°C
- Measuring accuracy
- ± 1.5 % of measuring range ± 0.3 % of measuring range end
- Reference medium / object
- Nitrogen
Connection technology
Cable sockets M12 5-pin field attachable
Cable sockets M12 5-wire shielded
Cable sockets M12-socket M12-connector 5-wire
Gateway
Process data acquisition
Other sensors
Protection cap, teflon M8
Recalibration of inline flow sensors
Manuals
Interfaces
Product Compliance
-
pdfUKCA declaration of conformityPDF-file, 325 KB
-
pdfMaterial compliancePDF-file, 477 KB
-
pdfEU declaration of conformityPDF-file, 253 KB
-
pdfUL declaration of conformityPDF-file, 254 KB
-
pdfCSA declaration of conformityPDF-file, 243 KB
Product flyers
Whitepapers
Application examples
| Classification | Class |
|---|---|
| eClass-7.0 | 27371815 |
| eClass-7.1 | 27371815 |
| eClass-8.0 | 27371815 |
| eClass-9.0 | 27371815 |
| eClass-9.1 | 27371815 |
| ETIM-6.0 | EC002580 |
| ETIM-7.0 | EC002580 |
| Property | Value |
|---|---|
| RoHS‑compliant | Yes |
| Reach-compliant | Yes |
| TSCA-compliant | Yes |
| IPF Product Group | 725 compressed air and leakage measurement |
| packaging dimensions | |
| customs tariff number | 90268020 |
| WEEE number | 40951076 |